by ETI Staff | Jun 2, 2021 | Frequently Asked Questions, TRACON
TRACON FAQ’S – FPT-130 CAN THE UNIT INTERFACE WITH BMS? CAN IT COMMUNICATE WITH BACNET OR MODBUS? No, the FPT 130 provides a summary alarm via a dry contact relay. This relay is energized whenever the unit is powered. So, with power off the NC contact is...
by ETI Staff | May 25, 2021 | Frequently Asked Questions, NETCOM FAQs
HOW CAN I CHANGE THE PRESSURE SETTINGS ON MY NETCOM? Establish communications with the dehydrator through the Ethernet interface (default IP address from the factory is 192.168.52.9) and navigate to the configuration page. Here you can change the low pressure alarm,...
by ETI Staff | Jan 24, 2021 | Controller, Frequently Asked Questions, Sensors, snow melting management, Snow Switch
WHY DO I HAVE A RED GFEP LIGHT ON? The GFEP indicator will come on when a ground fault occurs in one of the heater circuits. The insulating resistance of the heater cable is breaking down or the cable has been damaged allowing current to pass to ground thru an...
by ETI Staff | Oct 29, 2020 | Frequently Asked Questions, GPT 130 FAQs, News, TRACON
Temperature Controller – GPT-130 QUESTION – WHY AM I GETTING A GROUND FAULT WHEN THE GROUND FAULT CURRENT IS SO LOW? ANSWER – The GPT-130 displays a number of alarms, beside the ground...
by ETI Staff | Aug 6, 2020 | Controller, Frequently Asked Questions, Sensors, Snow & Ice Sensors FAQs, snow melting management, Snow Switch, Troubleshooting, Weather
Snow & Ice Systems – APS-3C QUESTION – Can I simulate a sensor call for heat to test the system? ANSWER – Yes, by putting a jumper between pins 1 and 2 of the class two...